Q7 ASD Installation and Operation Manual
Communications Speed #1
Program
⇒
Comm Settings
⇒
Comm Speed 1
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
for further information on this setting.
This parameter sets Communications Speed #1.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq.
Units — Hz
Communications Speed #2
Program
⇒
Comm Settings
⇒
Comm Speed 2
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
for further information on this setting.
This parameter sets the Communications Speed #2.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Commercial Power Wait Time
Program
⇒
Special Controls
⇒
Comm Wait Time
This parameter determines the amount of time that the drive will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
Parameter Type — Selection List
Factory Default — 0.62
Changeable During Run — No
Minimum — 0.37
Maximum — 10.00
Units — Seconds
Cooling Fan Control
Program
⇒
Protection
⇒
Cooling Fan Ctrl
This parameter sets the cooling fan run-time command.
Settings:
Automatic
Always On
Parameter Type — Selection List
Factory Default — Automatic
Changeable During Run — Yes
CPU Revision
Program
⇒
Utility Group
⇒
CPU Revision
This is a read-only parameter that displays the revision level of the CPU.