Q7 ASD Installation and Operation Manual
125
Units for Voltage and Current
Program
⇒
Utility Group
⇒
Units for V/I
This parameter sets the unit of measurement for current and voltage values
displayed on the keypad.
Settings:
%
V/A
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Upper Deviation Limit
Program
⇒
Feedback Settings
⇒
Upper Dev Limits
This parameter determines the maximum amount that the feedback may
increase the output signal.
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Upper Limit Frequency
Program
⇒
Fundamental #1
⇒
Upper Limit Freq
This parameter sets the highest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD may output frequencies
higher than the Upper Limit Frequency (but, lower than the Maximum
Frequency) when operating in the PID Control mode, Torque Control mode,
or the Vector Control modes (sensorless or feedback).
Note: This setting may not be higher than the Maximum
Frequency setting.
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
User Unit #1
Program
⇒
Utility Group
⇒
User Unit #1
The displayed unit of measurement may be changed from the Hz default setting
to any of the available characters for the frequency-display screen.
may be used to complete the unit of measurement display.
Note: Program
⇒
Utility Group
⇒
Frequency Multiplier must be
a non-zero value to use this feature.
Parameter Type — Alpha-Numeric
Factory Default — None
Changeable During Run — Yes
User Unit #2 – 5
Program
⇒
Utility Group
⇒
User Unit #2 – 5
See User Unit #1 for information on this parameter.