Q7 ASD Installation and Operation Manual
79
ON Terminal
Program
⇒
Input Terminals
⇒
On Terminal
This parameter selects the functionality of the ON discrete input virtual
terminal.
As a virtual terminal, the ON control terminal exists only in memory and is
considered to always be in its True (or connected to CC) state.
It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to 1 of the 69 possible
functions that are listed in
.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
OUT1 Off Delay
Program
⇒
Terminal Delays
⇒
OUT1 Off Delay
Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
).
The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 On Delay
Program
⇒
Terminal Delays
⇒
OUT1 On Delay
Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 Terminal
Program
⇒
Output Terminals
⇒
OUT1 Terminal
This parameter sets the functionality of the OUT1 (A & C) output contacts to 1
of the 58 possible functions that are listed in
.
The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Damper Cmd
Changeable During Run — No