Q7 ASD Installation and Operation Manual
Fault Detect Station
Program
⇒
Comm Settings
⇒
Fault Station
In a multiple-ASD configuration this setting determines the ASD responsible
for fault notification.
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 64
F Terminal
Program
⇒
Input Terminals
⇒
F Terminal
This parameter selects the functionality of the F discrete input terminal.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable F terminal to 1 of the 69 possible
functions that are listed in
.
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
F Terminal Delay
Program
⇒
Terminal Delays
⇒
F Delay
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
FL Off Delay
Program
⇒
Terminal Delays
⇒
FL Off Delay
This parameter delays the response of the FL output terminals by the
programmed value.
The on and off delay times of the FL terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS