Q7 ASD Installation and Operation Manual
75
Maximum Voltage #1
Program
⇒
Fundamental #1
⇒
Max Voltage #1
This parameter sets the applied output voltage at the Base Frequency and is the
maximum value of the output voltage of the ASD for the #1 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Maximum Voltage #2
Program
⇒
Fundamental #2
⇒
Max Voltage #2
This parameter sets the applied output voltage at the Base Frequency and is the
maximum value of the output voltage of the ASD for the #2 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Maximum Voltage #3
Program
⇒
Motor Settings
⇒
Max Voltage #3
This parameter sets the applied output voltage at the Base Frequency and is the
maximum value of the output voltage of the ASD for the #3 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Maximum Voltage #4
Program
⇒
Motor Settings
⇒
Max Voltage #4
This parameter sets the applied output voltage at the Base Frequency and is the
maximum value of the output voltage of the ASD for the #4 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Mode 1/2 Switching Frequency
Program
⇒
Freq Settings
⇒
Mode 1/2 SW Freq
This parameter sets the threshold frequency that will be used in the Reference
Priority Selection parameter to determine if Frequency Mode #1 or #2 will
control the output of the ASD.
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — Max. Freq.
Units — Hz