II-25
(2) Flow Measurement Relation
a.
Change measuring unit
Display Menu No.
: INP-121 : MULTIPLIER
Display Menu No.
: INP-122 : FLOW UNIT
Multiplier Options
:
x10
-6
, x10
-3
, x1, x10
+3
, x10
+6
, x10
+9
Measuring Unit Options
:
m
3
/D, m
3
/h, m
3
/min, m
3
/s, L/h, L/min, L/s, t/D, t/h, t/min, t/s,
kg/h, kg/min, kg/s,
Mft
3
/D, ft
3
/D, ft
3
/h, ft
3
/min, ft
3
/s, Mgal/D, gal/D, gal/h, gal/min, gal/s,
Mbbl/D, bbl/D, bbl/h, bbl/min, bbl/s, Macf/D, acf/D, acf/h, acf/min, acf/s
Use mass unit
In case of using mass unit (ex. kg/h etc.), it is necessary to input the liquid density, as follows.
b. Change fluid density
Display Menu No.
: INP-123 : DENSITY
Initial value
: 1.000
Range of Input
: 0.100 to 9.000
This parameter shall be required in case that Mass Unit (t, kg) is selected in the menu
INP-122 : FLOW UNIT.