III-32
Table 2; Selectable value and default of each parameters
Parameters Value
Range
Default
Description
MODE 0:
D-OUT
1: MODBUS
0: D-OUT
Protocol Selection
BAUD RATE
0: 4800bps
1: 9600bps
2: 19200bps
1: 9600bps
Baud Rate of DIGITAL Port1
PARITY 0:
EVEN
1: ODD
2: NONE
0: EVEN
Parity of DIGITAL Port1
MODBUS ADRESS
000
~
247
001 MODBUS
Slave
Address
INTERVAL
1 - 3600
1second
Data Interval at D-OUT MODE
Note: “D-OUT” is default digital output by original protocol which defined as chapter III-2-6.
(5) Supported Function Code
5-1. Function Code
Supported function code is as table 3 of below.
Table 3; Function Codes
Code Name
Supported
01
Read Coil Status
Yes
02
Read Input Status
Yes
03
Read Holding Register
Not Available
04 Read
Input
Register
Yes
05
Force Single Coil
Not Available
06
Preset Single Register
Not Available
07
Read Exception Status
Not Available
08 Diagnostics
Yes
11
Fetch Communication Event Counter
Yes
12
Fetch Communication Event Log
Not Available
13 Program
Controller
Not
Available
14 Poll
Controller
Not
Available
15
Force Multiple Coils
Not Available
16
Preset Multiple Registers
Not Available
17
Report Slave ID
Not Available
18 Program
884/M84
Not
Available
19
Reset Comm. Link
Not Available
20
Read General Reference
Not Available
21
Write General Reference
Not Available
22
Mask Write 4x Register
Not Available
23
Read/Write 4x Registers
Not Available
24
Read FIFO Queue
Not Available
Содержание UFL-30
Страница 1: ...Doc No KF08 001J Ultrasonic Flowmeter UFL 30 Installation Operation Manual ...
Страница 11: ... 10 blank ...
Страница 12: ...I Installation ...
Страница 60: ...II Operation ...
Страница 109: ...II 50 blank ...
Страница 110: ...III Other ...
Страница 123: ...III 14 III 2 5 Dimensions Main Unit ...
Страница 128: ...III 19 blank ...
Страница 129: ...III 20 blank ...
Страница 145: ...III 36 blank ...
Страница 165: ...III 56 blank ...