7 Alarms and messages
MIRUS Controller, SW 2.03.02, Additional Information Master (en-GB)
7-21
7.4.4 Messages during On-Call mode
Messages generated during the On-Call mode are shown on the screen as follows:
No.
Message
Set condition
Required user
action
Device action
C01
Power up test and
System test
successfully
completed on
(date) at (time).
To continue
please choose a
menu button on
the right.
Power up test and
System test
successfully
finished.
None.
Stays in On-Call
mode until user
activates one of
the tags.
C02
Mains supply lost!
Restore mains
supply or the
device will turn off
automatically.
AC lost.
Connect AC line
supply or turn off
MIRUS Controller
via Turn off button.
Operates on
battery. Performs
turn OFF
sequence after
user selection or if
AC isn't restored
within 30 seconds,
the system will
shut down into
OFF state.
Power up test and System test
successfully completed on
11.01.2013 at 10:25:00.
To continue please choose a
menu button on the right.
HW 2.n
SW 2.03.02
Содержание Mirus MC DES
Страница 1: ...Additional Information MIRUSTM Controller Software version 2 03 02 Hardware version 2 n...
Страница 28: ...1 Introduction 1 22 MIRUS Controller SW 2 03 02 Additional Information Master en GB Notes...
Страница 48: ...3 General description 3 8 MIRUS Controller SW 2 03 02 Additional Information Master en GB Notes...
Страница 78: ...5 Operation 5 18 MIRUS Controller SW 2 03 02 Additional Information Master en GB Notes...
Страница 92: ...6 Cleaning and maintenance 6 14 MIRUS Controller SW 2 03 02 Additional Information Master en GB Notes...
Страница 118: ...7 Alarms and messages 7 26 MIRUS Controller SW 2 03 02 Additional Information Master en GB Notes...