7 Alarms and messages
MIRUS Controller, SW 2.03.02, Additional Information Master (en-GB)
7-19
No.
Message
(in order of
testing)
Set condition
Required user
action
Device action
B13
Sorry. A problem
has been
detected. The
device cannot be
operated. To turn
off the device
please confirm.
A technical failure
was recognized
during System
test.
Confirm to turn off
MIRUS Controller.
Then disconnect
from AC, wait until
Alarm lights are
off, then reconnect
and re-start the
MIRUS Controller.
Contact your
service in case the
MIRUS Controller
will continue to
show this
message.
Performs turn OFF
sequence as soon
as user confirms
message.
B14
Thank you!
Goodbye...
This message is
sent whenever the
system is turned
off.
n/a
Performs turn OFF
sequence.