(15) Multi-Function Contact Input Selection (Sn-15~Sn-18)
• Select the set values shown below for Sn-15 to -18.
Terminal No
Sn-
Terminal 5
15
Terminal 6
16
Terminal 7
17
Terminal 8
18
Set Value
Function
LCD display (English)
Description
00
FWD / REV RUN select
3-wire RUN
3-wire sequence mode
Open:
FWD run,
(00 set in Sn-15) terminal 1- run,
Closed:
REV run,
2-stop, 5 FWD / REV selection
01
Operation signal select
Local / Remote
LOC / REMOT control
Open:
Operation according to the setting of Sn-04
1st ,2nd digits and Sn-08 1 st ,2 nd digits.
Closed:
Operation by frequency reference and run
command from digital operator. (Local mode)
02
Option / AC Drive
Open:
Operation by the operation or frequency
referemce select
Opt. Card Switch
reference from option card.
Closed:
Operation by the operation or frequency
reference from AC Drive.
03
Multi-step speed reference 1
Multi-Fct Command 1
Combination of multi-step speed references 1, 2 correspond to speed
04
Multi-step speed reference 2
Multi-Fct Command 2
reference (master speed AN-01) and speed references 2 to 4 (An-02 to 04)
05
Multi-step speed reference 3
Multi-FCT Command 3
Refer to “SYSTEM CONSTANT MULTI-STEP SPEED REFERENCE LIST”
06
Jog frequency reference select
JOG Command
Closed: Jog frequency reference is selected.
07
Accel / decel time select
Acc.&Dec. Switch
Open:
Accelerates / decelerates with ACCEL time 1 and DECEL
time 1. (Bn-01, Bn-02 set values)
Closed:
Accelerates / decelerates with ACCEL time 2 and DECEL
time 2. (Bn-03, Bn-04 set values)
08
External baseblock (No-
Ext. B.B. NO-Cont.
Closed:
AC Drive output is shut off. (Frequency
contact input)
reference is held.)
09
External baseblock NC (contact
Ext. B.B. NC-Cont.
Open:
AC Drive output is shut off. (Frequency
Input)
reference is held.)
0A
Accel / decel speed prohibit
Inhibit Acc.&Dec.
Frequency reference is held. (SFS operation is stopped.)
command (HOLD command)
0B
AC Drive overheat alarm
Over Heat Alarm
Closed:
Over Heat OH2 blinks on operator and
operation continues. (Minor fault)
2-46
PA 7300
PART II: OPERATION MANUAL
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...