3-8
PA 7300
PART II: OPERATION MANUAL
FAULT CONTACT
ERROR CAUSES
ACTION TO BE TAKEN
OUTPUT
Non Operation
–
–
• AC Drive KVA setting (Sn-01) error
• Parameter setting range error
• Multi-function contact input setting error
• Review the parameter setting range and
Non Operation
(Sn-15 ~ Sn-18)
and conditions
• Improper setting of V/F characteristic
(Cn-02 ~ Cn-08)
• Improper setting of carrier frequency
(Cn-23 ~ Cn-25)
Non Operation
• EEPROM internal data did not match when initializing the constant
• Turn off power, then turn on again. If error is
persistent, replace the control board.
• RS-485 communication option card fault.
• Turn off power, then turn on again. If error is
Non Operation
• Excess vibration or shock.
persistent, replace the option card.
• External noise
Non Operation
• The RS-485 communication protocols setting in AC Drive
• Check the setting in Sn-24 and option card
(Sn-24) and option card are in consistent.
• Check for communication cable between
Non Operation
• Poor connection
• communication option card and master
• Defective communication software (in master controller)
controller (PLC)
• Check for communication software.
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...