Function
Parameter
Name
LCD Display
Description
Factory
Reference
Number
(English)
Setting
Pages
- - -0:
External fault input (terminal 3 ):
NO-contact input
- - -1:
External fault input: NC-contact input
- -0 -:
External fault signal: always detected
- -1 -:
External fault signal: detected during
run only
Protective
00- -:
External fault detected: Ramp to
Sn-12
Characteristics
Sn-12=0100
stop (major fault) by Bn-02 set value
0100
2-44
Selection 3 (External
Extermal Faul
01- -:
External fault detected: Coast to
Fault Signal Function)
stop (major fault)
10- -:
External fault detected: Ramp to
stop (major fault) by Bn-04 set value
Protective
11- -:
External fault detected: operation to
Characteristic
continue (minor fault)
Select
- - -0:
Input phase loss protection
function ineffective
- - -1:
Input phase loss protection
function effective
Protective
- -0 -:
Output phase loss protection
Characteristics
Sn-13=0000
function ineffective
0000
2-44
Sn-13
Selection 4 (phase Loss
Phase Loss & Fan - -1 -:
Output phase loss protection
2-45
Protection and Cooling
Cont.
function effective
Fan ON/OFF Control)
- 0- -:
Cooling fan runs while AC
Drive power ON
- 1- -:
Cooling fan runs when heat sink
temperature exceeds 50°C
- - -0:
Motor overload (OL1)
protection effective
- - -1:
Motor overload (OL1)
Protective
protection ineffective
Characteristics
Sn-14=0000
- -0 -:
Motor overload protection: s
Sn-14
Selection 5
Over Load Select
tandard motor
0000
2-45
(Electronic Thermal
- -1 -:
Motor overload protection:
Overload Protection)
AC Drive duty motor
- 0- -:
Motor overload protection time
constants are standard time (8 minutes)
- 1- -:
Motor overload protection time
Sn-15
Terminal 5 Function
Sn-15=03
00~66
Terminal 5 (factory preset for
Term. 5 Function
multi-step speed reference 1)
03
Sn-16
Terminal 6 Function
Sn-16=04
00~66 Terminal 6 (factory preset for
04
Term. 6 Functio
multi-step speed reference 2)
2-46
Sn-17
Terminal 7 Function
Sn-17=06
00~66 Terminal 7 (factory preset for jog
06
~
Term. 7 Functio
frequency reference)
2-55
Sn-18
Terminal 8 Function
Sn-18=08
00~66 Terminal 8 (factory preset for
08
Multi-Function
Term. 8 Functio
external baseblock by NO contact input)
Select
Sn-19 Terminal AUX Function
Sn-19=00
00~0C Terminal AUX (factory preset for
00
2-56
Multi-Fct Input
auxiliary frequency command)
2-57
Sn-20
Terminal R2A-R2C
Sn-20=00
00~0F Terminal R2A-R2C (factory preset for run)
00
Function
Term. R2A Function
Sn-21
Terminal D01
Sn-21=01
00~0F Terminal D01 (factory preset for
01
2-58
Function
Term. D01 Function
zero speed)
~
Sn-22
Terminal R1A
Sn-22=02
00~0F Terminal R1A (factory preset for
02
2-61
Function
Term. R1A Function
Agreed frequency)
2-27
PA 7300
PART II: OPERATION MANUAL
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...