2.4 System Parameters Sn-
Function Parameter
Name
LCD Display
Description
Factory
Reference
No.
(English)
Setting
Page
Capacity
Sn-01
AC Drive Capacity
Sn-01=29
AC Drive Capacity Selection
*1
2-30
Setting
460V 25HP
2-31
V/f Curve
Sn-02
V/f Curve Selection
Sn-02=2
V/f Pattern Selection
2
2-32
V/f Curve
0000: Setting and reading of An- , Bn-
, Cn- , Sn- enabled
0101: Setting and reading of An-,
Operator
Sn-03
Operation Status
Sn-03=0000
Reading of Bn- ,Cn- ,
0000
2-33
Status
Sn- enabled
Operate Setting
1110: Contents Initialization (2-wire)*2
1111: Contents Initialization (3-wire)*2
1000: Initialize Un-11 contents
1001: Initialize Un-12 contents
- - -0: Frequency Command = Control
circuit terminals VIN or AIN
- - -1: Frequency Command = Frequency
Command 1 (An-01)
Operation Mode
- -0 -: RUN/STOP Command = Control
2-34
Sn-04
Select 1
circuit terminals
0011
2-35
(RUN - STOP
Sn-04=0011
- -1 -: RUN/STOP Command = Digital Operator
2-36
Selection)
Stopping Method
00- -: Stopping method = Ramp to stop
01- -: Stopping method =Coast to stop
10- -: Stopping method = Full-range DC
injection braking stop
11- -: Stopping method = Coast to stop
(timer function provided)
- - -0: Stop key effective during operation
from control terminal
- - -1: Stop key disabled during operation
Operation
Operation Mode
from control terminal
Mode
Sn-05
Selection 2
Sn-05=0000
- -0 -: Reverse run enabled
Select
(I/O Terminal
I/O Term Function
- -1 -: Reverse run disabled
Function Selection)
- 0- -: Control input terminals 1~8 are
0000
2-37
scanned twice.
-1- -: Control input terminals 1~8 are
scanned once.
0 - - -: Digital operator key = key function
1- - -: Digital operator key
= L/R (Local/Remote) function
- -00: S curve=0.2sec
- -01: S curve=0.0sec (NO S curve)
- -10: S curve=0.5sec
- -11: S curve=1.0sec
-0 - -: Reference command direct
Operation Mode
characteristics
Selection 3
Sn-06=0000
(0-10V or 4-20mA/0~100%)
2-38
Sn-06
(S-curve and
S-curve
-1 - -: Reference command inverse
0000
2-39
Frequency Reference
& Cmd. Char.
characteristics
2-40
Characteristics)
(0-10V or 4-20mA/100~0%)
0- - -: Stop by reference input when
frequency reference is missing
1- - -: Operation to continue at 80% of
frequence reference when
frequency reference is missing
2-25
PA 7300
PART II: OPERATION MANUAL
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...