App-3
PA 7300
APPENDIX
B. PID CONTROL
a. Constants related to PID Control Mode
The table below shows the constants used in the PID control mode.
CONSTANTS USED IN PID CONTROL MODE
FUNCTION
PARAMETER
NAME AND DESCRIPTION
LCD DISPLAY
UNIT
SETTING RANGE
FACTORY
NO
(ENGLISH)
SETTING
An-01
Setting of set point 1
An-01=060.00Hz
(Frequency command 1)
Frequency command 1
0.01Hz
0.00~180.00Hz
60.00Hz
An-02
Setting of set point 2
An-02=000.00Hz
(Frequency command 2)
Frequency command 2
0.01Hz
0.00~180.00Hz
0.00Hz
An-03
Setting of set point 3
An-03=000.00Hz
Setting of
(Frequency command 3)
Frequency command 3
0.01Hz
0.00~180.00Hz
0.00Hz
PID Control An-04
Setting of set point 4
An-04=000.00Hz
set
(Frequency command 4)
Frequency command 4
0.01Hz
0.00~180.00Hz
0.00Hz
points
An-05
Setting of set point 5
An-05=000.00Hz
(Note 1)
(Frequency command 5)
Frequency command 5
0.01Hz
0.00~180.00Hz
0.00Hz
An-06
Setting of set point 6
An-06=000.00Hz
(Frequency command 6)
Frequency command 6
0.01Hz
0.00~180.00Hz
0.00Hz
An-07
Setting of set point 7
An-07=000.00Hz
(Frequency command 7)
Frequency command 7
0.01Hz
0.00~180.00Hz
0.00Hz
An-08
Setting of set point 8
An-08=000.00Hz
(Frequency command 8)
Frequency command 8
0.01Hz
0.00~180.00Hz
0.00Hz
An-09
Setting of set point 9
An-09=006.00Hz
(Frequency command 9)
Jog command
0.01Hz
0.00~180.00Hz
6.00Hz
Bn-13
Setting of feedback
Bn-13=01.00
adjustment (PID Detection Gain)
PID Gain
0.01
0.01~10.00
1.00
Bn-14
Setting of proportional Gain (P)
Bn-14=01.0
PID P-Gain
0.1
0.0~10.0
1.0
Setting of Bn-15
Setting of integral time (I)
Bn-15=010.0S
PID Control
PID I-Time
0.1S
0.0~100.0S
10.0S
Constant
Bn-16
Setting of differential time (D)
Bn-16=0.00S
PID D-Time
0.01S
0.00~1.00S
0.00S
Bn-17
PID offset adjustment
Bn-17=000%
(PID Bias)
PID Bias
1%
0~109%
0%
Cn-43
PID integral upper Bound
Cn-43=100%
PID I-Upper
1%
0~109%
100%
Cn-44 PID
primary delay time constant
Cn-44=0.0S
PID Filter
0.1S
0.0~2.5S
0.0S
Integral
Sn-15-
Integral value reset by external
value reset Sn-18-
contact signal
–
–
–
–-
PID Control Sn-15-
PID Control Canceled by external
Cancel
Sn-18
contact signal
–
–
–
–
PID Control Sn-19
Sn-19 PID Control mode is
selection
entered by setting Sn-19=09
–
–
–
–
Control
On-04=0000
status 4
On-04
Selection of PID Control Mode
Control status 4
1
0000~1111
0000
(Note 1) The unit and setting range of An-
■ ■
can be changed according to the setting of the operator display
mode (Cn-20) as shown in the table above.
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...