(3) Operation status (Sn-03)
• Passwords (Sn-03=0000 or 0101)
The ability to set or read the different groups of constants is determined by Sn-03
as shown below.
Sn03
DRIVE mode
PRGM mode
To be set
To be monitored
To be set
To be monitored Only
0000*1
An, Bn
Sn, Cn
An, Bn,Sn, Cn
--
0101*2
An
Bn, Sn, Cn
An
Bn, Sn, Cn
*1: Factory setting
*2: When in DRIVE mode, the parameter groups Sn-, and Cn- can only be monitored if the
key and the keys are to be pressed at the same time.
*3: After a few trial operations and adjustment, Sn-03 should be set to “ 1111” to prevent
unwanted changes.
• Constant Initialization (Sn-03=1110 or 1111)
Except for parameters Sn-01~02, the parameter groups An- Bn- , Cn- , Sn- and On-
can be initialized to factory settings. At the same time, terminals 5~8 can be set as 2-wire or 3-wire
operation mode by varying the setting of Sn-03 (please see 2-/3-wire operation mode on
page 2-46).
• Special mode (Sn-03=1010)
The order parameters On- can be set and read when setting Sn-03 to 1010. After changing or
monitoring any of the On- parameters, please set Sn-03=0000 or 0101.
• Initialize the contents of monitoring parameters Un-11 and Un-12 (Sn-03=1000 and 1001)
The motor elapsed run hours (Un-11) and motor elapsed energy KWHR (Un-12)
can be reset by Sn-03 to 1000 and 1001 individually.
• The LCD display, in response to each setting is shown below.
Sn-03 Setting
LCD Display
0000
Sn-03=0000
Allow Setting
0101
Sn-03=0101
Inhibit Setting
1110
Sn-03=1110
2-Wire Initialize
1111
Sn-03=1111
3-Wire Initialize
1000
Sn-03=1000
Reset Un-11
1001
Sn-03=1001
Reset Un-12
2-33
PA 7300
PART II: OPERATION MANUAL
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...