(5) Operation Mode Select 2 (Sn-05)
• 1st digit
Select processing to be performed when the keypad STOP key is pressed during run via
control circuit terminals.
1st digit = 0: During run via control circuit terminals, the keypad STOP key is accepted.
If the STOP key is depressed, the AC drive stops according to the setting of
the 3rd and 4th digits of Sn-04 while the STOP LED indicator blinks. This stop
command is held until both the FWD run command and REV run command
of the control circuit terminals become “open”, or another frequency reference
is selected in the multi-step speed command or jog frequency reference section.
1st digit = 1: During run via control circuit terminals, the STOP key from the operator is
not accepted.
•
2nd digit
(REV run prohibited)
2nd digit = 0: REV run command from control circuit terminals or the digital operator
is accepted.
2nd digit = 1: REV run command from control circuit terminals or the digital operator is
not accepted.
•
3rd digit
(selection of double scanning of sequence command)
3rd digit = 0: The sequence command (control circuit terminals I to 8) is scanned twice.
3rd digit = 1: The sequence command (control circuit terminals I to 8) is scanned once.
•
4th digit
( key functions select )
4th digit=0 : The digital operator key is used as JOG key function.
(the JOG key function is enabled under Local mode )
4th digit=1 : The digital operator key is used as a Local/Remote (L/R) switch key.
* At the local mode, the AC drive operates by frequency reference and
run command from the digital operator.
* At the Remote mode, if selected, the multi-function contact inputs
(terminal 5 ~ 8 ) can act as Local/Remote operation signal (i.e. the set
value of Sn-15~18 is 0 1)
1. If terminal 5 ~ 8 =are open (Remote mode), the AC drive operates according
to the settings of Sn-04 1st, 2nd digits and Sn-08 1st ,
2nd digits (i.e. the key is used as a Remote key function.)
2. If terminal 5 ~ 8 are closed (Local mode), the AC drive operates by frequency
reference and run command from the digital operator. (i.e. the Remote key
function invalid)
* The Local/Remote (L/R) key function is enabled only when the drive
is stopped.
2-37
PA 7300
PART II: OPERATION MANUAL
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
PRGM
DRIVE
DSPL
FWD
REV
RESET
EDIT
ENTER
RUN
STOP
JOG
(L/R)
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...