2-11
PA 7300
PART II: OPERATION MANUAL
2.3 Control Parameters Cn-
Function Parameter
Name
LCD Display (English)
Setting Range
Setting
Factory
Reference
No.
Unit
Setting
Page
Cn-26
Overtorque Detection
Cn-26=160%
30 ~ 200%
1%
160%
OVER-
Level
Over Tq. Det Level
2-17
Torque
Cn-27
Overtorque Detection
Cn-27=00.1V
0.0 ~ 25.5s
0.1s
0.1s
Detection
Time
Over Tq. Det Time
Cn-28
Stall prevention Level
Cn-28=150%
30 ~ 200%
1%
150%
During Acceleration
ACC. Stall
Stall
Cn-29
Not Used
Cn-29=000
00 ~ 000
--
--
--
Prevention
Reserved
Cn-30
Stall Prevention Level
Cn-30=130%
30 ~ 200%
1%
130%
2-17
Frequency
Running Stall
Commun-
Cn-31
Communication Fault
Cn-31=01.0s
0.1 ~ 25.5s
0.1s
1s
2-18
ication Fault
Detection Time
Comm. Flt Det. Time
Cn-32
Frequency Detection
Cn-32=000.0Hz
0.0 ~ 180.0Hz
0.1Hz
0.0Hz
2-18
Frequency
1 Level
Freq Det. 1 Level
Detection
Cn-33
Frequency Detection
Cn-33=000.0Hz
0.0 ~ 180.0Hz
0.1Hz
0.0Hz
2 Level
Freq. Det. 2 Level
Cn-34
Not Used
Cn-34=0
0 ~ 0
--
--
--
--
Reserved
Cn-35
Not Used
Cn-35=0.0
0.0 ~ 0.0
--
--
Reserved
Fault
Cn-36
Number of Auto
Cn-36=00
0 ~ 10
1
0
2-19
Retry
Restart Attempts
Retry Times
2-24
Ride-thru
Cn-37
Power Loss Ride-thru
Cn-37=2.0s
0 ~ 2.0s
0.1s
2.0s*
4
2-19
time
Time
Ride-thru Time
Cn-38
Speed Search
Cn-38=150%
0 ~ 200%
1%
150%
Detection Level
SP_Search Level
Cn-39
Speed Search
Cn-39=0.20s
0.1 ~ 25.5s
0.1s
2.0s
Speed
Time
SP_Search Time
2-20
Search
Cn-40
Min. Baselock Time
Cn-40=1.0s
0.5 ~ 5.0s
0.1s
1.0s*
4
Control
Min B.B Time
Cn-41
V/F Curve in Speed
Cn-41=100%
10 ~ 100%
1%
100%
Search
SP_Search V/F Curve
Cn-42
Voltage Recovery
Cn-42=0.3s
0.1~ 5.0s
0.1s
0.3s
Time
Voltage Recovery
Cn-43
PID Integral Upper
Cn-43=100%
0 ~ 109%
1%
100%
2-21
PID
Bound
PID I-Upper
Control
Cn-44
PID Primary Delay
Cn-44=0.0s
0.0 ~ 2.5s
0.1s
0.0s
Time Constant
PID Filter
Cn-45
Energy-Savings Voltage
Cn-45=120%
0 ~ 120%
1%
120%
Upper Limit (60Hz)
Level 60Hz
Energy-
Cn-46
Energy Savings Voltage
Cn-46=16%
0 ~ 25%
1%
16%
Savings
Upper Limit (6Hz)
Level 6HZ
Voltage
Cn-47
Energy Savings Voltage
Cn-47=050%
0 ~ 100%
1%
50%
2-21
Unit
Lower Limit (60Hz)
Level 60HZ
Cn-48
Energy Savings Voltage
Cn-48=12%
0~ 25%
1%
12
%
Lower Limit (6Hz)
Level 6HZ
Содержание PA7300 Series
Страница 9: ......
Страница 10: ...PART I INSTALLATION MANUAL ...
Страница 44: ...PART II OPERATION MANUAL ...
Страница 107: ...2 57 PA 7300 PART II OPERATION MANUAL REDUCTION COEFFICIENT ...
Страница 116: ...2 66 PA 7300 PART II OPERATION MANUAL 2 5 Monitoring Peramiters UN ...
Страница 117: ...2 67 PA 7300 PART II OPERATION MANUAL ...
Страница 150: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 151: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 152: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 153: ...i PA 7300 INSTRUCTION MANUAL ...
Страница 154: ...5100 N IH 35 Round Rock Texas 78681 USA 1 800 279 4007 www tecowestinghouse com ...