11
Control command (set value=A)
• This contact is “closed” when the control command from the keyboard is selected.
12
Overtorque detection (set value=B)
• This contact remains “closed” as long as the AC drive is detecting overtorque. Set
overtorque detection level in Cn-26 and set overtorque detection time in Cn-27.
13
Frequency reference loss (set value=C)
• This is “closed” when loss of frequency reference is detected.
14
Not used (set value= D)
15
Fault (set value=E)
• This contact is “closed” when the AC drive detects a major fault. However, in the event
of a fault in the watchdog (OP Commu. Error 1 CPF00) or transmission between the
mainframe and operator, the AC drive does not operate.
16
Not used (set value=F)
• Set F in multi-function contact when the output is not used.
2-61
PA 7300
PART II: OPERATION MANUAL