Note:
The Inverter will stop accelerating or decelerating when Accel / Decel Prohibit Signal is activated.
When the signal is removed, the Inverter continues accelerating or decelerating.
Run
Command
Accel /
Decel *
Prohibit
Output
Time
* : When the “Run” Command is OFF, the Accel and Decel Prohibit Command is inactive.
External Emergency Stop
As soon as an External Emergency Stop signal is received, the Inverter will Decel to a stop. (Regardless
of the setting in (
Fn_44
), the display will blink "E.S." After this signal is removed, either turn OFF and
ON the RUN Command again to reset. The Inverter will restart from the Start Frequency. If the
Emergency Stop Signal is removed before the Inverter stops, the Inverter will still execute the
Emergency Stop.
Fault Contacts are Controlled by (
Fn_97
)
External Base Block Command
The Base Block Command can be found in the Multi-Function Input assignment group, (6).
As soon as Base Block signal is applied, the Inverter output is shut off regardless of the setting in
(
Fn_44
) and the display will blink "b.b.". After the Base Block input is removed, either turn OFF
and ON again Run Command, or press the RUN Key and the Inverter will restart from the Start
Frequency.