Fn_06:
Frequency Upper Limit
The maximum speed of the motor is adjusted by raising the Frequency Upper Limit at (
Fn_06
).
Fn_07:
Frequency Lower Limit
The minimum speed for the motor is adjusted by the Frequency Lower Limit at (
Fn_07
).
100%
Internal
Fn_06
(Frequency Upper Limit)
Frequency
Signal
Fn_07
(Frequency Lower Limit)
0%
Fn_08:
At Target Speed
0 - 400Hz
The Multi-Function Output (Terminals 10 & 11) can be programmed to close at a predetermined
target speed. (
Fn_65
) must be programmed to 1 and (
Fn_08
) must be programmed with the
desired target speed.
Fn_09:
Target Speed Bandwidth
0 - 30Hz
The Target Speed Bandwith function can be used to close the Multi-Function Output (Terminals 10
& 11) at (
Fn_61
). See Page 47
Target Speed +
Fn_9
/ 2 ---------------------------------------
Desired Target Speed ---------------------------------------
Target Speed -
FN_9
/ 2 ---------------------------------------
Note: Terminals 10 and 11 are Normally Open during Power OFF, and Normally Closed
during Power ON.