17
Function
Fn_
xx
Description
Engineering
Units
Range
Factory
Setting
Page
Dir / -
29
Positive / Negative Direction
1
0 : Positive
1 : Negative
0
32
Power Voltage
30
Input Voltage of Power Supply
0.1V
200 - 480V
*3
33
31
Momentary Power Loss Ride
Through Time
0.1 sec
.7 - 2 sec
0.5 sec
33
Momentary
Power Loss
Ride Through
32
xxx0 : Disable
xxx1 : Enable
0
33
33
Reserved for Future Use
33
34
Auto Restart Time
0.1 sec
0 - 800 sec
0 sec
33
Auto Restart
35
No. of Auto Restart Attempts
1
0 - 10
0
33
Motor Poles
36
No. of Motor Poles
2P
2 - 8 pole
4P
33
V/Hz Pattern
37
Max. Frequency
0.01Hz
50 - 400Hz
60 / 50Hz
34
38
Max. Voltage Ratio
0.1%
0 - 100%
100%
34
39
Mid. Frequency
0.01Hz
0.11 - 400Hz
3.0 /
2.5Hz
34
40
Mid. Voltage Ratio
0.1%
0 - 100%
7.5%
34
41
Voltage Ratio at 0.1Hz
0.1%
0 - 100%
7.5%
34
Starting Freq.
42
Start Frequency Adjustment
0.01Hz
0.1 - 10Hz
1Hz
35
Carrier Freq.
43
Carrier Frequency Adjustment
1
0 - 15
14
35
Stopping Mode
and Braking
Resistor
Protection
44
xxx0 : Decel to Stop
xxx1 : Coast to Stop
xx0x : Braking Resistor Thermal Protection disable
xx1x : Braking Resistor Thermal Protection enable
0000
35
45
Gain : Analog Output
1%
0 - 200%
100%
36
Multi-Function
Analog Output
Selection
(Terminals)
(14 & 15)
46
0 : Output Frequency (
Fn_6
Max.)
1 : Set Frequency (
Fn_6
Max.)
2 : Output Voltage
3 : Bus Voltage
0
36
Display Mode
47
xxx0 : Output Voltage (VAC) Display disable
xxx1 : Output Voltage (VAC) Display enable
xx0x : Bus Voltage (VDC) Display disable
xx1x : Bus Voltage (VDC) Display enable
x0xx : Output Current (IAC) Display disable
x1xx : Output Current (IAC) Display enable
0000
36