Functional Specification:
Carrier Frequency
1 - 12KHz
Frequency Control Range
0.1 - 400Hz
Frequency Accuracy
Digital: 0.01%; Analog: 0.4%
Frequency Resolution
Digital Keypad Reference: 0.01Hz (0 - 99.9Hz); 0.1Hz (100 - 400Hz)
Frequency Setting Signal
0 - 5VDC, 0 - 10VDC, 0 - 20mA, 4 - 20mA
Accel / Decel Time
0.1 - 3600 Seconds (Two Independent Accel / Decel or S-Curve Settings)
Braking Torque
Approx. 20% (Braking Transistor Unit is built-in to 10HP units and below)
Control
Character-
istics
V/F Pattern
18 Preprogrammed Patterns (One Custom Pattern)
Instantaneous Overcurrent
Approximately 200% of Rated Current
Overload Protection
150% Rated Output Current for 60 Seconds
Motor Overload
Electronic Thermal Overload Relay
Overvoltage
230V Series: (DC Bus exceeds 427V)
460V Series: (DC Bus exceeds 854V)
Undervoltage
230V Series: (DC Bus Voltage drops below 200V)
460V Series: (DC Bus Voltage drops below 400V)
Momentary Power Loss
.7 - 2 Seconds: FM100 can be restarted with Speed Search
Protection
Function
Heatsink Overheat
Protected by Thermostat
Operation Signal
Forward / Reverse Operation, by Keypad or Hardwired Contact,
Multiple Individual Commands
Reset
Released Protection while the Protect Function is Operating
Input
Signals
Multi-Functional
Inputs
Refer to Function Illustration in
Fn_56
Multi-Functional
Output
Refer to Function Illustration in
Fn_61
Output
Signal
Fault Contact
250VAC 1A, 30VDC 1A or less
Built-in Function
Frequency Reference Bias / Gain; Upper and Lower Limit; Manual Torque
Boost; Frequency Meter Gain; Auto Restart; Skip Frequency; S-Curve
Accel / Decel; Carrier Frequency Adjust; Communication Link Function
Digital Keypad Monitor
4 Digit 7 Segment LED Display Indicates: Frequency; Output Frequency;
Speed; Output Current; Output Voltage; Bus Voltage; Rotating Direction
Operating
Conditions
Analog Output Monitor
0 - 10VDC Analog Output, Possible to Select: Output Frequency; Setting
Frequency; Output Voltage; Bus Voltage
Location
Indoor (Protected from Corrosive Gases and Dust)
Ambient Temperature
+14
o
F ~ 104
o
F (-10
o
C ~ 40
o
C)
Humidity
0 - 95% (Non-Condensing)
Environ-
mental
Conditions
Vibration
0.5G (4.9m/s
2
)
Enclosure
NEMA 1
UL
UL508C