45
Fn_78
:
Overtorque Detection Level:
30 - 200%
Fn_79
:
Overtorque Detection Time:
0 - 25 sec
1. An Overtorque condition exists when the output current (rated current is 100%) remains above
Overtorque Detection Level (
Fn_78
) for a period greater than the Overtorque Detection Time
(
Fn_79
).
2. When Overtorque occurs and (
Fn_77
) is set to (x0xx), the Inverter continues to run and displays
a blinking “OL3” light until the output current is lower than the (
Fn_78
) setting.
When Overtorque occurs and (
Fn_77
) is set to (x1xx), the Inverter Base Blocks immediately and
the display blinks “OL3”. To restart the Inverter, press RESET key.
3. When (
Fn_61
) (
Fn_62
) or (
Fn_63
) (Multi-Function Output Terminal Control) is set to 05, the
Multi-Function Output provides an Overtorque Detection Signal. The Overtorque Detection
Output signal is available if (
Fn_77
) is set to (xxx1).
100% of Speed
100%
Torque
&
Horse-
Power
Current Detection