Function
Fn_
xx
Description
Engineering
Units
Range
Factory
Setting
Page
80
S-Curve Time 1 in the period of
Accel / Decel Time 1
0.1 sec
0 - 4 sec
0.2 sec
46
S-Curve
81
S-Curve Time 2 in the period of
Accel / Decel Time 2
0.1 sec
0 - 4 sec
0.6 sec
46
82
xx00: Energy Savings disable
xx01: Energy Savings controlled by Multi-Function Input
Terminals using the Preset Speed Functions
xx0x: Set Freq. Output after Process Timer finishes counting
0000
47
Energy
Savings
83
Energy Saving Gain
1%
0 - 100%
80%
47
Sequence
Control
84
xxx0 : Process Timer disable
xxx1 : Process Timer enable
xx0x : Set Freq. Output after Process Timer finishes counting
xx1x : Zero Speed Output after Process Timer finishes
counting
0000
48
85
Process Timer 1
0.1 sec
0 - 3600 sec
0 sec
49
86
Process Timer 2
0.1 sec
0 - 3600 sec
0 sec
49
87
Process Timer 3
0.1 sec
0 - 3600 sec
0 sec
49
88
Process Timer 4
0.1 sec
0 - 3600 sec
0 sec
49
89
Process Timer 5
0.1 sec
0 - 3600 sec
0 sec
49
90
Process Timer 6
0.1 sec
0 - 3600 sec
0 sec
49
Process Timers
91
Process Timer 7
0.1 sec
0 - 3600 sec
0 sec
49
Vibration
92
Vibration Control Times
1
1 - 100
5
49
Control
93
Vibration Control Gain
0.1%
0 - 100%
0%
49
94
Vibration Control Bias
1%
0 - 30%
0%
49
95
Parameters for Factory
Adjustment
50
96
Do Not Change
50
Fault Contact
Control
97
xxx0 : Fault Contact is Not energized during
Auto Restart Operation
xxx1 : Fault Contact is energized during
Auto Restart Operation
xx0x : Fault Contact is Not energized during
Momentary Power Loss Detection
xx1x : Fault Contact is energized during
Momentary Power Loss Detection
0000
50