38
Fn_53
:
DC Braking Time
0.1 ~
0 - 25.5 sec
Fn_54
:
DC Injection Braking Frequency
0.1 ~
0.1 - 10Hz
Fn_55
:
DC Braking Level
0.1% ~ 0 - 20%
Fn_56 - Fn_60
:
DC Braking Level
0.1% ~ 0 - 20%
The application parameters in the Multi-Function Input list are all assignable on
TM2
.
Terminals (6) (7) and (8) are the designated application terminals for the following features:
00: SP1 (Multi-Speed 1)
:
Please refer to (
Fn_17
)
01: SP2 (Multi-Speed 2)
:
Please refer to (
Fn_17
)
02: SP3 (Multi-Speed 3)
:
Please refer to (
Fn_17
)
03: Jog Operation
Please refer to (
Fn_17
)
04: Accel / Decel Time Selection
Please refer to (
Fn_01
)
05: External Emergency Stop
06: External Base Block Command
07: Speed Search:
Please refer to (
Fn_48
)
08: Energy Savings Mode:
Please refer to (
Fn_82
)
19: Control Signal Selection
10: Communication Control Mode Selection
11: Accel / Decel Prohibit
12: UP Command
13: DOWN Command
14: Sequence Control:
Please refer to (
Fn_17
) (
Fn_84
) - (
Fn_91
)
15: Master / Auxiliary Speed Selection:
Please refer to (
Fn_11
)
16: (NO - Normally Open Contact) to (NC - Normally Closed Contact)
Remarks: (
Fn_56
) will be ineffective when Terminal (6) is used for 3-Wire Control
There are 32 combinations that can be selected as above by
Terminals (6), (7), (8), (21), (22) (
Fn_56
) (
Fn_57
) (
Fn_58
).