UP / DOWN Command
RUN
UP
DOWN
Output Frequency
To utilize the Up and Down function, (
Fn_11
) must be set to terminal control.
When using this function, set (
Fn_03
) to the (0xxx) position. The Inverter will accelerate to the
Target Frequency set at (
Fn_25
) after the designated terminal is turned ON. The drive will remain
at what ever speed it was at when the contact terminal was released.
When the (UP) or (DOWN) terminal is engaged, the Inverter starts accelerating or decelerating.
When the UP or DOWN signal disappears, the Inverter will stay at the current frequency. Once the
operating signal is OFF, the Inverter will decelerate to a stop or stop immediately (decided by
(
Fn_44
)), the operation frequency will be recorded in (
Fn_25
).
Terminal UP or DOWN control is inactive during the stop mode. The Target Frequency must be
changed at (
Fn_25
) through the Keypad.
Fn_61
:
Multi-Function Output:
Terminals 10 / 11
00: Run Mode
01: At Target Speed
02: Set Frequency (
Fn_08
) (
Fn_09
)
03: Frequency Detection (
Fn_08
) 1
04: Frequency Detection (
Fn_08
) 2
05: Overcurrent Detection
06: Change From NO to NC Contact
Fn_25