50
Fn_97
:
Fault Control Setup
xxx0:
Fault Contact is Not energized during Auto Restart Operation
xxx1:
Fault Contact is energized during Auto Restart Operation
xx0x:
Fault Contact is Not energized during Momentary Power Loss Detection
xx1x:
Fault Contact is energized during Momentary Power Loss Detection
x0xx:
Fault Contact is Not energized after External Emergency Stop signal is received
x1xx:
Fault Contact is energized after External Emergency Stop signal is received
0xxx:
Fault Contact is Not energized during External Base Block
1xxx:
Fault Contact is energized during External Base Block
Fn_98
:
Fault Contact Setup
xxx0: Fault Contact is Not energized after Overtorque (OL3) is detected
xxx1:
Fault Contact is energized after Overtorque (OL3) is detected
xx0x:
Fault Contact is Not energized after Electronic Overload (OL1) is activated
xx1x:
Fault Contact is energized after Electronic Overload (OL1) is activated
x0xx:
Fault Contact is Normally Open (NO)
x1xx:
Fault Contact is Normally Closed (NC)
0xxx:
Fault Contact is Not energized after Electronic Overload (OL2) is activated
1xxx:
Fault Contact is energized after Electronic Overload (OL2) is activated
Note:
If (
Fn_97
) is set to (xxx0). During the Auto Restart operation, the fault contact will not be energized
until (
Fn_35
(Auto Restart Times) decreases to 0. (OL1 / OL2 / OL3)
Fn_100
:
Communication Address:
1 ~ 32
Fn_101
:
Baud Rate of Communication:
(bps)
0:
=
4800
1:
=
9600
2:
=
19200
3:
=
38400