30
Fn_16
:
Direct Start / Scanning / Reset Options
xxx0: Direct Start enable when Remote RUN Command is ON
xxx1: Direct Start disable when Remote RUN Command is ON
xx0x: Reset effective only if Remote RUN Command is OFF
xx1x: Reset effective regardless of the Remote RUN Command condition
00xx:
TM2
Terminal will scan 10 times
01xx:
TM2
Terminal will scan 5 times
10xx:
TM2
Terminal will scan 3 times
11xx:
TM2
Terminal will scan once
Note:
1. When (
Fn_16
) is set at (xxx1) and the operation mode is set for
TM2
Control (
Fn_10
), the
Inverter cannot start if the RUN switch is ON when the power is engaged. The “STP1” LED will
flash. On the Keypad, the RUN switch must be turned OFF and ON again, in order for the
Inverter to start.
2. Scanning the input signals at
TM2
on Terminals (3) (4) (5) (6) (7) (8) (9)
(FWD) (REV) (SP1) (SP2) (SP3) (RESET) are set at (
Fn_16
). If
TM2
detects the same input
signals for the programmed number of times in a row, the Inverter will recognize the signal as a
normal signal and execute it.
On the other hand, if
TM2
detects the same input signals that are less than the number of times
programmed,
TM2
will ignore the signal. Remark: The scan time is 2ms.
Preset Speeds and Timer Controls
Fn_17
:
Preset Speed 1:
0.01Hz ~
0 - 400Hz
Fn_18
:
Preset Speed 2:
0.01Hz
~
0 - 400Hz
Fn_19
:
Preset Speed 3:
0.01Hz
~
0 - 400Hz
Fn_20
:
Preset Speed 4:
0.01Hz
~
0 - 400Hz
Fn_21
:
Preset Speed 5:
0.01Hz
~
0 - 400Hz
Fn_22: Preset Speed 6:
0.01Hz
~
0 - 400Hz
Fn_23: Preset Speed 7:
0.01Hz
~
0 - 400Hz