Special Condition Indication
Fault Code
Content
Illustration
STP0
Zero Speed Stop 1.
Fn_11
= 0 or 3,
Fn_07
< 0.1Hz, and setting freq.< 0.1Hz;
Fn_11
= 1 or 23,
Fn_07
< (
Fn_06
/ 100), and setting freq.
< 0.1Hz
STP1
Direct Start
disable
1. Power switched on while remote RUN switched ON
(
Fn_10
)
Direct Start is prohibited (
Fn_16
= xxx1). Inverter
can not be started and will display STP1. (Refer to
Fn_16
)
Inverter can be started directly when
Fn_16
= xxx0.
STP2
Emergency Stop
Command by
STOP Key
1. Emergency Stop via Digital Keypad in remote control mode
(
Fn_10
= 1) by pressing STOP key (
Fn_48
= xx0x). Once
STOP key is pressed during operation, Inverter will stop
according to the setting of
Fn_44
and display STP2. Inverter
will not restart until power is turned OFF and ON again.
2. If the Inverter is under communications control and
FN_48
= xx0x, Once STOP key is pressed, Inverter will stop
according to the setting of
Fn_44
and display STP2. Inverter
will not restart until computer sends Stop command followed
by a RUN command.
3. STOP key cannot be used for Emergency Stop when
Fn_48
=xx1x.
E.S.
Emergency Stop
Command by
Remote Control
1. Emergency stop via remote control mode (Multi-Function
Input terminals), The Inverter will decelerate to stop and
display E.S.
b.b.
External Base
Block
External signal Base Blocks Inverter via Multi-Function Input
Terminals (please refer to
Fn_56-60
).