36
Fn_45
:
Multi-Function Adjustment for Analog Output
0 - 200%
(Meters)
Fn_46
:
Multi-Function Analog Output Meter Selection
0 - 3
Meter Scale Factor
0: Output Frequency
(
Fn_06
Max.)
10VDC / (
Fn_06
)
1: Set Frequency
(
Fn_06
Max.)
10VDC / (
Fn_06
)
2: Output Voltage
(VAC)
10VDC / (
Fn_30
)
3: Bus Voltage
(10VDC / 450VDC: for 230V Series)
(10VDC / 900VDC: for 460V Series)
Fn_47
:
Meter Display Mode
xxx0 :
Output Voltage Display
disable
xxx1 :
Output Voltage Display
enable
xx0x :
Bus Voltage Display
disable
xx1x : Bus Voltage Display
enable
x0xx : Output
Current
disable
x1xx : Output Current
enable
(Meters)
The Display contents can be switched back and forth using the Key. This can be
accomplished in either the RUN or STOP mode.
Frequency / RPM / Engineering Units (Mode set by (
Fn_51
))
Fxxx
(Parameters Setting Mode: Refer to Digital Keypad Illustration)
Output Voltage
Bus Voltage
(Output Voltage, Bus Voltage
Output Current), Power setup at
(
Fn_47
)
Output Current
DSPL
FUNC