24
Fn_03:
START / STOP Control From TM2
Fn-03
: START / STOP Control for Remote Operation
xxx0: FWD / STOP, REV / STOP
xx01: FWD / REV, RUN / STOP
xx10: 3-Wire Control
x0xx: REV Command enable
x1xx: REV Command disable
0xxx: During
Fn_11
= 3 (
TM2
up / down control).
The setting frequency will remain at the last operational frequency when stopped.
x1xx: During
Fn_11
= 3 (
TM2
up / down control).
Note:
1:
Fn_03
will be enabled only when
Fn_10
= 1(Remote Control).
2: The STOP” key on the Keypad can be use for Emergency Stopping at any time.
(Refer to Fn_48 for additional stopping functions)
Momentary START / STOP Switch:
Maintained FORWARD and REVERSE Switch:
Set: (
Fn_10
to 1)
Set: (
Fn_03
to 3-Wire Control) (XX10)
Maintained ON / OFF Switch:
Maintained FORWARD / REVERSE Switch:
Set: (
Fn_10
to 1)
Set: (
Fn_03
to (XX01))
Maintained FORWARD Switch:
Maintained REVERSE Switch:
Set: (
Fn_10
to 1)
Set: (
Fn_03
to (0000))