41
Fn_65
:
Skip Frequency 1
0.01Hz
~
0 - 400Hz
Fn_66
:
Skip Frequency 2
0.01Hz
~
0 - 400Hz
Fn_67
:
Skip Frequency 3
0.01Hz
~
0 - 400Hz
Fn_68
:
Frequency Band Width
0.01Hz
~
0 - 10Hz
Example:
When (
Fn_65
) is set at 10.0Hz, (
Fn_66
) is set at 20.0Hz, (
Fn_67
) is at 30.0Hz, (
Fn_68
)
Skip bandwidth at 2.0Hz
The Skip Frequency Ranges are:
10Hz
±
2Hz = 8 - 12Hz
20Hz
±
2Hz = 18 - 22Hz
30Hz
±
2Hz = 28 - 32Hz
Fn_69
:
Electronic Overload Protection
xxx0:
Electronic Thermal Motor Protection activated
xxx1:
Electronic Thermal Motor Protection deactivated
xx0x:
Electronic Thermal characteristics in accordance with Standard Motor
xx1x:
Electronic Thermal characteristics in accordance with Special Motor
x0xx:
Motor Protection OL: 103% continuous, 150% for 60 seconds
x1xx:
Motor Protection OL: 113% continuous, 123% for 60 seconds
0xxx:
Coast to Stop after Electronic Thermal Motor Protection is energized
1xxx:
Operation continued after Electronic Thermal Motor Protection is energized
Fn_70
:
Motor Rated Current
(- - - - -)
The motors Rated Nameplate Current must be entered in function (
Fn_70
) for proper thermal
protection.