Fn_84
:
Sequence Control
xxx0:
Process Timer disabled
xxx1:
Process Timer enabled
xx0x:
Set Frequency Output after Process Timer ends count
xx1x:
Zero Speed Output after Process Timer ends count
xx1x:
Process Sequence Auto Repeat
SP1 SP2 SP3
Frequency output
OFF OFF OFF
Set by external signal or
Digital operator control
ON
OFF OFF
Frequency of Fn_17
OFF ON
OFF
Frequency of Fn_18
ON
ON
OFF
Frequency of Fn_19
OFF OFF ON
Frequency of Fn_20
ON
OFF ON
Frequency of Fn_21
OFF ON
ON
Frequency of Fn_22
ON
ON
ON
Frequency of Fn_23
Note:
If (
Fn_84
) is set to (xxx1) and (
Fn_56
) (
Fn_57
) and (
Fn_58
) are set to (0) (1) or (2) when the
contact pulse is closed on one of the designated terminals the drive will run for the programmed
amount of time set in (
Fn_85
) through (
Fn_91
) and at a the programmed frequency set in (
Fn_17
)
through (
Fn_23
). At the end of the sequence if there is no other command, the Inverter will resume
its frequency command by the Keypad, Remote Speed Pot, or back to (
Fn_84
).
Note:
When (
Fn_84
) is set to (xxx0), the Inverter will operated under the Multi-Speed Frequency when
(
Fn_56
) (
Fn_57
) and
Fn_58
) are set to (0) (1) or (2).
For Process Sequence
Control, use the Process
Timers and the Preset Speed
functions.
(
Fn_85
) Through (
Fn_91
)
(
Fn_17
) Through (
Fn_23
)
Frequency
Output (HZ)
FWD or REV
Command
SP1 Terminal 6
SP2 Terminal 7
SP3 Terminal 8
time
Frequency
Output (HZ)
FWD or REV
Command
SP1 Terminal 6
SP2 Terminal 7
SP3 Terminal 8
time
Pulse signal
Operation
time