19
Function
Fn_
xx
Description
Engineering
Units
Range
Factory
Setting
Page
Skip
Frequency
65
Setting Prohibited Freq. 1
0.01Hz
0 - 400Hz
0Hz
41
Control
66
Setting Prohibited Freq. 2
0.01Hz
0 - 400Hz
0Hz
41
67
Setting Prohibited Freq. 3
0.01Hz
0 - 400Hz
0Hz
41
Bandwidth
68
Setting Prohibited Freq. Range 0.01Hz
0 - 10Hz
0Hz
41
Electronic
Thermal
Overload
Protection
69
xxx0 : Electronic Thermal Motor Protection enable
xxx1 : Electronic Thermal Motor Protection disable
xx0x : Electronic Thermal Characteristics in accordance
with a Standard Motor
xx1x : Electronic Thermal Characteristics in accordance
with a Special Motor
x0xx : Constant Torque
Inverter Protection OL : 103% Continuous
150% for 60 seconds
x1xx : Variable Torque
Inverter Protection OL : 113% Continuous
123% for 60 seconds
0xxx : Coast to Stop after Electronic Thermal Motor
Protection is energized
1xxx : Operation continued after Electronic Thermal
Motor Protection is energized
0000
41
Reference
Amps
70
Motor Rated Current
0.1A
-
Specs.
41
71
Torque Boost Selection
44
Torque Boost
72
Torque Boost Gain
0.1%
0.0 - 10.0%
0.0%
44
74
Reserved for Future Use
44
75
Motor No Load Current
44
Slip
Compensation
76
Motor Rated Slip
0.01Hz
0.00 - 6.00Hz
0.00Hz
44
77
xxx0 : Overtorque Detection disable
xxx1 : Overtorque Detection enable
xx0x : Enable only if at Set Frequency
xx1x : Enable during Operation
x0xx : Operation continued after Overtorque is Detected
x1xx : Coast to Stop after Overtorque is Detected
0000
44
78
Overtorque Detection Level
1%
30 - 200%
160%
45
Overtorque
Control
79
Overtorque Detection Time
0.1 sec
0 - 25 sec
0.1 sec
45