23
Function Description
Fn_00:
Drive Capacity Selection
= 1 - 18
FN_00
MODEL NUMBER
FN_00
MODEL NUMBER
01
230 Volt .50HP
10
460 Volt 1HP
02
230 Volt 1HP
11
460 Volt 2HP
03
230 Volt 2HP
12
460 Volt 3HP
04
230 Volt 3HP
13
460 Volt 5HP
05
230 Volt 5HP
14
460 Volt 7.5HP
06
230 Volt 7.5HP
15
460 Volt 10HP
07
230 Volt 10HP
16
460 Volt 15HP
08
230 Volt 15HP
17
460 Volt 20HP
09
230 Volt 20/30HP
18
460 Volt 30HP
Fn_01:
Acceleration Time
= 0.1 - 3600 Sec.
Acceleration time equals the time it takes the Inverter to go from 0 speed to target speed. The
Keypad on the Inverter will set the acceleration time.
Press the
(Key), press the up and down arrow keys to find (
Fn_01
).
Press the
(Key), press the up and down arrows to change the acceleration time.
Press the
(Key), again to store the setting.
Fn_02:
Deceleration Time
= 0.1 - 3600 Sec.
Deceleration time equals the time it takes the Inverter to go from one target speed to a slower
target speed. The programming of the Deceleration function is the same as the Acceleration
function above.
READ
ENTER
DATA
ENTER
DSPL
FUNC