Preparing for Server Installation
7
The minimum ceiling height for the cabinet is 230 cm (90 inches), measured from the
true floor or raised floor, whichever is higher. An additional 91.4 cm (36 inches) is for
top clearance. The space above the cabinet and its surroundings must not restrict the
movement of cool air between the air conditioner and the cabinet, or the movement
of hot air coming out of the top of the cabinet.
■
“Receiving and Unpacking Guidelines” on page 7
■
“Maintenance Space Guidelines” on page 8
Receiving and Unpacking Guidelines
The following table lists the dimensions and weights for the Sun Server X4-2
shipping carton.
When the Sun Server X4-2 is unloaded at your site, leave the server in its shipping
cartons until it arrives in its installation location. Use a separate area in which to
remove the packaging material to reduce particle contamination before entering the
data center. Ensure that there is enough clearance and clear pathways for moving the
Sun Server X4-2 from the unpacking area to the installation location. The entire
access route to the installation site should be free of raised-pattern flooring that can
cause vibration.
Depth Model 1242
Depth Model 1042
(front door handle to rear door
handle)
120 cm (47.24 inches)
105.8 cm (41.66 inches)
Weight Model 1242
Weight Model 1042
150.6 kg (332 lbs)
123.4 kg (272 lbs)
Maximum dynamic load
1005 kg (2215 lbs)
TABLE:
Shipping Carton Specifications
Requirement
Specification
Shipping carton height
26.0 cm (10.24 inches)
Shipping carton width
60.65 cm (23.88 inches)
Shipping carton length
99.0 cm (38.98 inches)
Shipping carton weight
5.65 kg (12.46 lbs)
TABLE:
Sun Rack II Models 1242 and 1042 Specifications
(Continued)
Requirement
Specification
Содержание Server X4-2
Страница 1: ...Sun Server X4 2 Installation Guide Part No E38019 04 February 2014...
Страница 10: ...x Sun Server X4 2 Installation Guide February 2014...
Страница 14: ...xiv Sun Server X4 2 Installation Guide February 2014...
Страница 18: ...4 Sun Server X4 2 Installation Guide February 2014...
Страница 44: ...30 Sun Server X4 2 Installation Guide February 2014...
Страница 122: ...108 Sun Server X4 2 Installation Guide February 2014...
Страница 160: ...146 Sun Server X4 2 Installation Guide February 2014 4 Click Virtual Drives The Virtual Drives screen appears...
Страница 162: ...148 Sun Server X4 2 Installation Guide February 2014...
Страница 172: ...158 Sun Server X4 2 Installation Guide February 2014...
Страница 206: ...192 Sun Server X4 2 Installation Guide February 2014...