6.3 Power Supply Plug Wiring
Connect the power supply plug to the 24VDC controller power supply according to instructions (1) (2)
and (3) and then insert it into the PWR connector of the controller.
(1) Wiring of power supply (C24V, M24V, 0V)
Connect the positive of the 24VDC controller power supply to the C24V and M24V and connect the
negative of that power supply to the 0V terminal.
(2) Wiring of the stop switch (EMG)
Stop switch must be installed by the user to stop the actuator in abnormal situations.
Refer to
6.4 Wiring of shutdown circuit for wiring.
(3) Wiring of the lock release (LK RLS)
Install an unlocking switch for adjustment or recovery during an emergency of the locking actuator.
Switch (24V DC, contact capacity 0.5A or more) is provided by customer.
One terminal of the lock release switch should be connected to the 24VDC power supply and the other
should be connected to the LK RLS terminal. When this is switched on, the lock will be released.
Caution
(1) Do not use a power supply with "inrush-current control" for the controller power supply.
(2) It is unnecessary to connect LK RLS terminal when the actuator does not have locking
mechanism.
(3) The LK RLS terminal is only used for adjustment and emergency return. It must not be energized
during normal operation.
External shut
down circuit
Unlocking
Switch
Power supply plug
LK RLS (6)
(1) C 24V
(2) M 24V
0V (4)
(3) EMG
24VDC
0V
Controller
Input power
supply