- 88 -
No.JXC#-OMX0009-A
Controller
supply
voltage is
outside set
range.
(01-147)
Over
CrtlVol
D
RESET
SVON
<Contents>
The control power supply voltage within the controller is outside the set
range.
<Countermeasure>
Make sure that the voltage supplied to the control power (C24V) of the
controller is appropriate.
Caution
If a single power supply is used for both the control power and the
motor power, or the power supply is "inrush-current control type", a
power voltage drop may be caused due to a voltage drop during
acceleration/deceleration.
Current limit
is exceeded
(01-148)
Over load
D
RESET
SVON
<Contents>
The output current accumulated value exceeds the specified value.
<Countermeasure>
Make sure there are no obstructions that interfere with the electric
actuator movement. Also, make sure that the load, speed, acceleration
and deceleration are within the range of the electric actuator.
The target
position was
not reached
within the set
time limit
(01-149)
Posn
failed
ALM
D
RESET
SVON
<Content>
Failed to reach the set position within the set time limit.
<Content>
Make sure there are no obstructions that interfere with the
electric actuator movement. Also, make sure that the load,
speed, acceleration and deceleration are within the range of the
electric actuator.