- 85 -
No.JXC#-OMX0009-A
Set step data
is not
registered on
list.
(01-051)
Step data
ALM2
B
RESET
<Contents>
For an operation for a specific step data no., the requested number of
the step data is not registered. (When operation is commanded
through PLC, this alarm will be generated depending on the signal
interval and the holding time of signals)
< Countermeasure >
(1) Make sure that the “Movement MOD” in the step data is not "Blank
(Disabled)" and that numbers [1(ABS)] and [2(INC)] or input in the
numerical instruction operation.
(2)
Set the interval time between signals to more than twice the
communication cycle time, when signals are to be continuously
input, because PLC processing delays and controller scanning
delays can occur.
Refer to
15.1[2] Positioning operation
.
Set stroke is
outside the
stroke limit.
(01-052)
Stroke limit
B
RESET
<Contents>
The actuator goes outside the stroke limit specified by the basic
parameters, "Stroke (+)" and "Stroke (-)" if it performs the requested
operation. (Including JOG operation after return to origin)
<Countermeasure>
Make sure that the basic parameters, "Stroke (+)" and "Stroke (-)" are
consistent with the distance of actuator movement specified in the step
data.
Caution
If the operation method of step data is INC, take care with the
position where operation starts and the travel distance.
Alarm
_Comment
_058
(01-058)
3A
B
RESET
<Content>
This alarm occurs when the following parameter is outside of the
settable range during the numerical instruction operation.
(Settable range)
(1) AREA 1 < AREA 2
( If both Area1 and Area2 are 0, the alarm will not be activated.)
(2) Trigger LV
≦
Pushing force
(3) Minimum speed of actuator
≦
Pushing speed
≦
Speed
(4) Pushing speed
≦
Maximum pushing speed of actuator
(5) Pushing force
≧
Minimum pushing force of actuator
(6) Basic parameter "Maximum pushing force"
≧
Minimum pushing
force of the actuator
(7) Basic parameters "Maximum pushing force"
≧
Trigger LV
<Countermeasure>
Modify the basic parameter setting.
Caution
Please refer to the operation manual or catalog of the
actuator for the maximum pushing speed, minimum pushing
force, and minimum speed for the actuator.
Alarm
_Comment
_061
(01-061)
3D
B
RESET
<Content>
This alarm occurs when specifying step data based on the
unregistered No. of the step data or when the numbers of the
Movement MOD specify outside of range during numerical instruction
operation. (When operation is commanded through PLC, this alarm will
be generated depending on the input signal interval and the holding
time of signals)
<Countermeasures>
(1) Make sure that the “Movement MOD” in the step data is not
"Blank (Disabled)" and that numbers [1(ABS)] or [2(INC)] are
input in the numerical instruction operation.
(2)
Set the interval time between signals to more than twice the
communication cycle time, when signals are to be continuously
input, because PLC processing delays and controller scanning
delays can occur.
Refer to
15.1 [2] Positioning operation
.