No.JXC#-OMX0009-A
16.2 Alarms and countermeasures
Controller
setting software
(code)
1
Teaching box
G
r
o
u
p
How to
deactivate
Alarm contents/Countermeasure
Drive data
value is
wrong
(01-048)
Step
dataALM1
B
RESET
<Condition>
The step data is incorrect for the following conditions
(Settable range)
(1) Area1 <Area2
(If both Area1 and Area2 is 0, the alarm will not be activated.)
(2) Trigger LV ≤ Pushing force
(3) Minimum speed of actuator ≤ Pushing speed ≤ Speed
(4) Pushing speed ≤ Maximum pushing speed of actuator
(5) Pushing force ≤ Minimum pushing force of actuator
(6) Basic parameter "Maximum pushing force" ≥Minimum pushing
force of the actuator
(7) Basic parameters "Max pushing force" ≥ Threshold
<Countermeasure>
Modify the step data and basic parameters setting
Caution
Please refer to the manual or the catalogue of the actuator for the
max/min pushing force/speed for the actuator.
Parameter
value is
wrong
(01-049)
Parameter
ALM
B
RESET
<Contents>
The basic parameter is not correct for the following condition:
(Settable range)
(1) Stroke(-) < Stroke (+)
(2) W-Area 1 < W-Area 2
(
If both W-Area1 and W-Area2 is 0, the alarm will not be
activated.)
(3) Maximum pushing force < Maximum pushing force of actuator
<Countermeasure>
Modify the basic parameter setting.
Caution
Please refer to the manual or the catalogue of the actuator for the
maximum pushing force for the actuator.
The
deceleration
value is too
small.
(
01-050
)
Small Dec
B
RESET
input
<Contents>
Step data in which a deceleration speed exceeding the stroke
limit is specified.
<Countermeasure>
Modify the Deceleration value to a value with a sufficient margin
so that the electric actuator can stop within the stroke limit.