- 43 -
No.JXC#-OMX0009-A
(3) Controller
→
Higher level device [IN] (Remote to Master)
PLC
memory
address
Signal name
Description
Rx
Single
numerical data
instructions
Half numerical
data
instructions
Full numerical
data
instructions
00
OUT0
When the operation is started and “DRIVE” is turned
OFF, the step No. executed by “DRIVE” will be
refreshed/updated by the combination of “OUT0” to
“OUT5” (binary digit).
(E.g.) Step data No.3 is output
OUT5
OUT 4
OUT 3
OUT 2
OUT 1
OUT 0
OFF
OFF
OFF
OFF
ON
ON
Caution
(1) When “RESET” is turned ON, these signals turn OFF.
(2) During the alarm, these signals output the alarm group.
(3) During the pushing operation, if the actuator runs over
the defined pushing width, these signals turn OFF.
01
OUT1
02
OUT2
03
OUT3
04
OUT4
05
OUT5
06
-
-
07
-
-
08
BUSY
This signal is ON during the movement of the electric
actuator (during the positioning operation, etc.).
Caution
During the pushing operation without movement (no
movement but the electric actuator generating the pushing
force), BUSY is OFF. BUSY signal stays on for 50ms or
longer after operation starts.
09
SVRE
When the servo motor is OFF, “SVRE” is OFF. When
the servo motor is ON, “SVRE” is ON.
0A
SETON
When the actuator is in the SETON status (the position
information is established), this signal turns ON.
When the position status is not established, this signal
is OFF.