W-AREA1
“
Stroke (-)
”
to
“
Stroke (+)
”
of the basic
parameter
This is the setting to define the conditions where the WAREA will be
turned ON. [Unit: mm]
If the current position is within the range between the W area end 1 and
W area end 2, the WAREA will be turned ON.
* If W area output end 1 >W area output end 2, the alarm “Parameter
ALM” will be activated. However no alarm is generated if W area end
1= W area end 2 = 0, the WAREA will be turned OFF
XX
W-AREA2
“
Stroke (-)
”
to
“
Stroke (+)
”
of the basic
parameter
XX
ORG Correct
Fixed value
This is a fixed value for the controller. Do not change the setting.
(Default value is
“
0
”
)
-
Sensor type
Fixed value
This is a fixed value for the controller. Do not change the setting.
(Default value is
“
2
”
)
-
Option 1
(Occupied
number of
stations of CC-
Link)
1,2,4
Set the operation mode for the controller (number of occupied
stations).
Parameter
Operation mode
(number of occupied stations)
1
Single numerical data instruction mode
(1 stations is occupied)
2
Half numerical data instruction mode
(2 stations are occupied)
4
Full numerical data instruction mode
(4 stations are occupied)
X
Undefined
parameter No.11
(Operation
setting at CC-
Link
communication
error)
0, 10
Set the operating method of CC-Link communication
abnormality (time-out, malfunction, and CRC error).
Parameter
Output the
data to
control unit
Details
0
Hold
(Hold the
operating
state)
Even if communication abnormality
occurs in CC-Link, the alarm does
not occur.
The control unit continues
operation and executes it.
10
Alarm stop
When the communication
abnormality occurs in CC-Link, the
control unit will be stop state by the
alarm and outputs
“Communication alarm 150”.
X
Undefined
parameter No.12
Fixed value
This is a fixed value for the controller. Do not change the setting.
(Default value is
“
0
”
)
-
*1) The actuator model determines the available input values. Refer to the operation manual of the actuator
for details.
*2) It is recommended to set the “maximum speed” for the
electric actuator operation. Control is
restricted so that the set value is not exceeded. The response will be slower because of this.
*3) For the basic parameter "Parameter protection" to "3: Step", set it according
to the following procedures.
1. Start controller-setting software (JXC-W2) in the Normal mode.
2. Select "HELP" - "Password" from the menu and input "password" in the password input screen.
3. Change the basic parameter "Parameter protection" to "3: Step" in the
Parameter window.
4. Click "Download" to transmit the change. The text colour of the changed parameter will change
from blue to black.
5. After completing the setting, turn the JXCM1 OFF then ON to make the change effective.