4.9.2.2
TCP connection monitoring
Ethernet interface > Advanced options > TCP connection monitoring
●
TCP connection monitoring time
Function: If there is no data traffic within the TCP connection monitoring time, the TIM
sends a keepalive to the communications partner.
Default setting: 10 s. Permitted range: 1...65535 s
●
TCP keepalive monitoring time
After sending a keepalive, the TIM expects a reply from the communications partner
within the keepalive monitoring time. If the TIM does not receive a reply within the
configured time, it terminates the connection.
Default setting: 1 s. Permitted range: 1...65535 s
4.9.2.3
Transmission settings
Transmission settings
●
Send conditional spontaneous frames as blocks
Indicates the form of transfer of data frames with the transmission mode "Conditional
spontaneous".
–
Option enabled
Several data items are collected and sent only when a frame is filled to the maximum.
–
Option disabled
The data is transmitted spontaneously as a single frame.
The transmission mode "Conditional spontaneous" is set differently for the TD7 versions:
–
TD7onTIM
In the "Trigger" tab of the data point (data point editor)
–
TD7onCPU
Via the "Unconditional" parameter of the data point typicals (TD7 blocks)
●
Max. allowed disruption time
Tolerance time (s) for a detected connection disruption.
If there is still a disruption on the connection when the set time has elapsed, the
disruption is signaled to all accessible connection partners of the disrupted station.
Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...