Configuration
4.22 Data points
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
117
Note
Fast setting of triggers
Triggers must not be set faster than a minimum interval of 500 milliseconds. This also
applies to hardware triggers (input area).
Note
Hardware trigger
You need to reset hardware triggers via the user program
Transferring the value of a data point configured as an event
You specify whether the value of a data point is transferred to the communications partner
immediately after the trigger fires or after a delay in the "Transmission mode" parameter.
Transmission mode
The transmission mode of a frame is set in the "Trigger" tab of the data point. With the
option, you specify whether messages of events are sent immediately or following a delay:
●
Spontaneous (unsolicited - direct transfer)
The value is transferred immediately.
●
Conditional spontaneous (buffered transfer)
The value is transferred only when one of the following conditions is fulfilled:
–
The communications partner queries the station.
–
The value of another event with the transmission mode "Spontaneous" is transferred.
–
The fill level of the send buffer has reached 90% of its maximum capacity.
Enable archiving
Allows the retentive saving of events on the SD card of the S7-1500 CPU when there are
connection disruptions.
Archiving can be enabled under the following conditions:
●
The transmission mode of the data point is "Every value triggered".
●
The "Enable retentive saving" option is selected in the parameter group "Basic settings >
Retentive saving of events" of the TIM.
For information on the options and mechanisms of the parameter, see section Configuration
(Page 58).
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...