Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
216
Operating Instructions, 02/2018, C79000-G8976-C468-02
Name:
MaxInputTime
Declaration: INPUT
Data type:
INT
Range of val-
ues:
•
0
Value for unrequired parameter
•
1 ... 32000
Range of values for monitoring time
Explanation: Monitoring time in ms for commands and setpoints that are input via hard-
ware.
A monitoring time of at least 30 s is recommended.
If you do not require the parameter, specify 0 (zero).
Name:
ResetError
Declaration: INPUT
Data type:
BOOL
Range of val-
ues:
Input
I 0.0 ... I n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation: Input for resetting the output GlobalCmdOutputError.
If you do not require the parameter, specify a memory or data bit that always
has signal 0.
Name:
InputOK
Declaration: OUTPUT
Data type:
BOOL
Range of val-
ues:
Output
Q 0.0 ... Q n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation: Display of the enabling of hardware commands and setpoints
Has a 1 signal as soon as the current entry was enabled, i.e. when the hard-
ware command or setpoint was entered correctly.
The display bit goes off when the entry is reset, in other words when the
command key is released or the setpoint entry key "EnterInput" input is re-
leased.
If you do not require the parameter, specify a memory or data bit in the
memory area of the local data.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...