Cyclic OB1
Data point typicals Following the FCs for SINAUT basic tasks, data point typicals for sending and
receiving data are called. The sequence of the individual typicals is unimportant.
The number of typicals to call and the required types depend on the amount and
type of data to be sent and received.
The following typically applies to a station:
•
The following are sent:
–
Binary information, such as status messages and alarms
–
Analog values
–
Counted values
•
The following are received:
–
Commands
–
Setpoints, limit values, parameters
Bin04B_S
One or more FBs for the acquisition and transfer of binary information, such as
messages, alarms, etc.
Ana04W_S
One or more FBs for the acquisition and transfer of analog values
Cnt01D_S /
Cnt04D_S
One or more FBs for the acquisition and transfer of counted values
A requirement for the use of the FBs is that FC PulseCounter is included in a
cyclic interrupt OB, e.g. OB35. This FC is responsible for the time-driven acquisi-
tion of counted pulses in the background.
Cmd01B_R
One or more FBs for receipt and output of commands.
Set01W_R /
Par12D_R
One or more FBs for receipt and output of setpoints, limit values or parameters..
Dat12D_S /
Dat256D_S
One or more FBs for the acquisition and transfer of 12 data double words with
any content.
There is no data-specific processing and change control for these typicals. The
user program is responsible for this. As an option change control can be activat-
ed that triggers a transfer with each bit change.
TD7 programs for master stations and node stations
In principle, the TD7 programs of master stations and node stations look the same as for a
station. The corresponding receive typicals are used in a master station for the send typicals
of a station.
In a node station, both send typicals and the corresponding receive typicals are used
according to the transmission direction.
In the master station it is practical to structure the OB1 program according to stations, in
other words, all data typicals belonging to the same station are called in one FC. The best
overview is provided when the number of the FC is identical to the subscriber number of the
station.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...