Configuration
4.22 Data points
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
125
Set limit value 'low' / Set limit value 'high'
Requirements for the function
●
Configuration of the threshold trigger for this data point
●
PLC tag in the bit memory operand area or data area
The analog value data point must be linked to a PLC tag in the bit memory or data area
(data block).
For PLC tags for analog input modules (input operand area) limit value configuration is
not possible. With these analog values the limit values of the following table are used
automatically.
The configuration of limit values is pointless for measured values that have already been
preprocessed on the CPU.
Function
In these two input boxes, you can set a limit value in the direction of the start of the
measuring range or in the direction of the end of the measuring range. You can also
evaluate the limit values, for example as the start or end of the measuring range.
Configuration of the limit value
The limit value is configured as a whole decimal number. The range of values is based on
the range of values of the raw value of analog input modules.
Range
Raw value (16 bits) of the PLC tag
Module output [mA]
Measuring
range [%]
Decimal
Hexadecimal
0 .. 20
(unipolar)
-20 .. +20
(bipolar)
4 .. 20
(life zero)
Overflow
32767
7FFF
> 23.515
> 23.515
> 22.810
> 117.593
Overrange
32511
...
27649
7EFF
...
6C01
23.515
...
20.001
23.515
...
20.001
22.810
...
20.001
117.593
...
100.004
Nominal range
(unipolar / life zero)
27648
...
0
6C00
...
0000
20
...
0
20
...
4
100
...
0
Nominal range (bipolar)
27648 ...
0
... -27648
6C00 ...
0000
... 9400
20 ...
0
... -20
100 ...
0
... -100
Underrange
(unipolar / life zero)
-1
...
-4864
FFFF
...
ED00
-0.001
...
-3.518
3.999
...
1.185
-0.004
...
-17.59
Underrange (bipolar)
-27649
...
-32512
93FF
...
8100
-20.001
...
-23.516
-100.004
...
-117.593
Undershoot / wire break
-32768
8000
< -3.518
< 1.185
< -17.593
Please note: The entry of the value 0 (zero) is interpreted as a deactivated limit value.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...