LEDs, connectors, switches, card slot
2.4 Switch
TIM 1531 IRC
36
Operating Instructions, 02/2018, C79000-G8976-C468-02
●
MRES
Maintenance status
The setting "MRES" is adopted by pressing and holding down the switch in this position
(button function).
By pressing the switch for at least 5 seconds, the functions described below are
triggered. If you release the switch before the 5 seconds have elapsed, the TIM shows no
reaction.
Functions:
–
Restart
When the switch is pressed in STOP mode
The TIM restarts.
–
Reset to factory settings
Only when the switch is pressed during a restart
The TIM is reset to the factory settings. Note the effects of the reset, particularly the
deletion of the configuration data.
For information on the effects of resetting, refer to the section Resetting to factory
Functions in the setting "MRES"
Functions when holding the switch in the "MRES" setting for at least 5 seconds:
Table 2- 6
Button functions
Function
Previous setting or action
Effect
Restart
Pressing the switch from the "STOP"
setting
The TIM restarts.
Release the switch at the beginning of
the restart.
Reset
Pressing the switch after triggering a
restart
The TIM is reset to the factory set-
tings. All the configuration data is
deleted.
For the relevant LED patterns see the following section:
●
Startup - LED pattern (Page 49)
●
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...