Configuration
4.10 Serial interface > Advanced options
TIM 1531 IRC
78
Operating Instructions, 02/2018, C79000-G8976-C468-02
Time options
●
Call acceptance delay
Wait time (s) before accepting an incoming call
Due to the wait time acceptance of the call is possible for the TIM when a telephone is
connected to a shared telephone connection to the TIM.
Default setting: 0. Permitted range: 0...30
●
Dial test interval
The test interval (min) is started when no connection could be established by the TIM
after 3 attempted repetitions. When the test interval elapses, the TIM re-establishes the
connection again.
If it fails to establish the connection again, the test interval is restarted.
If a new message is pending for transfer during the test interval in a master station TIM,
the TIM attempts to establish a connection immediately.
Default setting: 5. Permitted range: 0...255
●
Minimum connection duration
Only for interfaces with the Network node type "Master station".
Minimum connection duration (s) for a dial-up connection.
The minimum connection duration may be required in fast dial-up networks to be able to
wait for the reply during a general request before the connection is terminated.
Default setting: 5. Permitted range: 0...65535
●
Abort delay time
Duration (s) a dial-up connection is retained when the send buffer of the TIM is full and
the TIM can send no further messages or data to the CPU.
During the abort delay time, received messages are acknowledged negatively and the
communications partner repeats sent and negatively acknowledged messages.
When the abort delay time elapses, the connection is terminated.
Default setting: 20. Permitted range: 0...255
Event transmission
●
Type of transmission
Specifies the form in which data messages are sent.
–
As single messages
–
Several messages as a block
Mobile wireless settings
●
PIN
PIN of the SIM card of the modem MD720
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...