Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
251
If the OB1 cycle time is lower than 1 second (this is normal) the output is set exactly at the
programmed second value with the inaccuracy of the OB1 cycle time of less than 1 s.
If the OB1 cycle time is higher than 1 seconds, the FC works with a tolerance of 4 seconds.
If the FC is processed too late but still within 4 seconds of the configured time, the output is
still set.
The edge memory bit "Flag" configured for the FC is set at the same time as the output and
reset 5 seconds after the configured time.
No placeholder parameter may be used for the edge memory bit and it must not be reset by
the user program.
You can find examples of the parameter assignment for FC Trigger further below.
Parameter
Name:
IntervalMode
Declaration: INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Explanation Point in time / time interval
•
FALSE = point in time
•
TRUE = time interval
You will find examples of the parameter assignment for a time or time interval
after this explanation of the parameters.
Name:
Hour_Minute
Declaration: INPUT
Data type:
WORD
Explanation Specifies the values for hours and minutes.
Further explanation: Refer to the parameter "Month_Year".
Name:
Second_Day
Declaration: INPUT
Data type:
WORD
Explanation Specifies the values for seconds and day.
Further explanation: Refer to the parameter "Month_Year".
Name:
Month_Year
Declaration: INPUT
Data type:
WORD
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...